SCB,
SSB,
SCBH & SCBV SWAY BRACE ANCHORS
SRC ROD STIFFENER CLAMP, SCBA ASSEMBLY,
CCB CLEVIS CROSS
BRACE
SAB &
SAS ANCHOR BOLTS
Through the use of aircraft cable with
swivel anchors, piping, ductwork and suspended equipment can be
safely prevented from swinging out of control during earthquakes
or when exposed to wind.
Cable braces are designed so when they
are installed with sufficient slack they do not interfere with neoprene
or spring isolator function but effectively control movement, preventing
equipment detachment and excessive damage.
Mason Type
SCB Data Sheet
TYPE SCB ASSEMBLY
RATINGS AS CONTROLLED BY CABLE BREAK STRENGTH
| Size |
Cable
Dia.
(in) |
OSHPD
Max.
Ratings
(lbs.) |
SCB-1
SCB-2
SCB-3
SCB-4 |
1/8
3/16
1/4
3/8 |
975
2050
3150
6875 |
Ratings are from test data and calculations
used to obtain California OSHPD Preapproval Number R-0202.
Testing was supervised and certified by an independent engineer
registered in the state of California.
Ratings are based on attachment to steel.
Ratings will be controlled by attachment
methods to concrete.
SCB ANCHOR DIMENSIONS
(inches)
| Size |
A |
B |
C |
D |
E |
F |
G |
H |
|
SCB-1
SCB-2
SCB-3
SCB-4
|
1 3/8
1 5/8
2
3 1/8 |
2
2 3/4
3 1/2
5 |
1
1 3/8
1 3/4
2 1/2 |
15/16
1 3/16
1 7/16
1 15/16
|
3 3/8
4 3/8
4 3/4
5 3/4
|
1 1/2
1 3/4
2
2 1/4 |
9/16
11/16
13/16
1 5/16
|
1/2
5/8
3/4
1
|
Mason Type
SSB Data Sheet
Swivel ended anchors simplify installations
as braces do not have to be cut to exact length. The anchor
will swivel to provide solid anchorage when bolting.
TYPE SSB ANCHOR
RATINGS
| Size |
OSHPD
MAX.
Ratings
(lbs.) |
SSB-1
SSB-2
SSB-3
SSB-4 |
1500
3000
5000
8750 |
Ratings are from test data and calculations
used to obtain California OSHPD Preapproval Number R-0202.
Testing was supervised and certified by an independent engineer
registered in the state of California.
Ratings are based on attachment to steel.
Ratings will be controlled by attachment
methods to concrete.
SSB ANCHOR DIMENSIONS
(inches)
| Size |
A |
B |
C |
D |
E |
F |
G |
H |
|
SSB-1
SSB-2
SSB-3
SSB-4
|
1 3/8
1 5/8
2
3 1/8 |
2
2 3/4
3 1/2
5 |
1
1 3/8
1 3/4
2 1/2 |
15/16
1 3/16
1 7/16
1 15/16
|
3 3/8
4 3/8
4 3/4
5 3/4
|
1 1/2
1 3/4
2
2 1/4 |
9/16
11/16
13/16
1 5/16
|
9/16
9/16
9/16
11/16
|
Mason Type
SCBH Data Sheet
Cables can only be used in tension so a
hook does not slide off. A hooked end provides for quick attachment
to hanger rods without removing clevis bolts or trapeze rods.
TYPE SCBH ASSEMBLY
RATINGS AS CONTROLLED BY CABLE BRAKE STRENGTH
| Size |
Cable
Dia.
(in) |
OSHPD
Max.
Ratings
(lbs.) |
|
SCBH-1
SCBH-2
SCBH-3
|
1/8
3/16
1/4 |
975
2050
3150 |
Ratings are from test data and calculations
used to obtain California OSHPD Preapproval Number R-0202.
Testing was supervised and certified by an independent engineer
registered in the state of California.
Ratings are based on attachment to steel.
SCBH assemblies will fit rod sizes as tabulated.
Preferred installation angle is 45 degrees.
Maximum variation +15 degrees.
TYPE SCBH ANCHOR
DIMENSIONS (inches)
| Size |
For use with
Rod Sizes |
A |
B |
C |
D |
E |
F |
G |
H |
|
SCBH-1
SCBH-2
SCBH-3
|
1/2, 5/8
3/4, 7/8
1, 1 1/81/2, 5/8
3/4, 7/8
1, 1 1/8
|
1 7/8
2 7/8
3 1/2 |
2 3/8
3 3/4
4 3/4 |
1
1 3/8
1 3/4 |
1
1 3/16
1 7/16
|
3 3/8
4 3/8
4 3/4
|
1 1/2
1 3/4
2 |
5/8
7/8
1 1/8
|
1/2
5/8
3/4
|
Mason Type
SCBV Data Sheet
The SCBV can be used with either an SCB
or SCBH on the other end. Clamping to beam flanges eliminates
drilling or welding and generally presents a cost savings.
TYPE SCBV ASSEMBLY
RATINGS AS CONTROLLED BY CABLE BRAKE STRENGTH
| Size |
Cable
Dia.
(in) |
OSHPD
Max.
Ratings
(lbs.) |
|
SCBV-1
SCBV-2
SCBV-3
|
1/8
3/16
1/4 |
975
2050
3150 |
Ratings are from test data and calculations
used to obtain California OSHPD Preapproval Number R-0202.
Testing was supervised and certified by an independent engineer
registered in the state of California.
Ratings are based on attachment to steel.
SCBH assemblies will fit rod sizes as tabulated.
Preferred installation angle is 45 degrees.
Maximum variation +15 degrees.
NOTE: Not to be used as a vertical
hanger for equipment, ductwork or piping. To be used as a
seismic restraint only.
TYPE SCBV ANCHOR
DIMENSIONS (inches)
| Size |
VICE JAW |
A |
B |
C |
D |
E |
F |
G |
Beam Flange
Width Range
(in) |
| Width |
Clearance |
Depth |
|
SCBV-1
SCBV-2
SCBV-3
|
11/16
7/8
1 1/16
|
11/16
1 1/16
1 1/8 |
1 5/16
1 1/16
1 15/16 |
1 7/8
2 7/8
3 3/8 |
2 3/8
3
3 3/4
|
7/16
1/2
5/8 |
1 1/2
1 3/4
2
|
1/2
5/8
3/4
|
3/8
3/8
1/2 |
10
12
12
|
3 1/2 - 8 1/2
3 1/2 - 10
4 - 9 1/2
|

Controlling sway is frequently not enough
to insure safety. Rod stiffeners such as angle attached with
seismic rod clamps (RSC) prevent suspended rods from buckling from
vertical movements. Mason isolation hangers which have vertical
limit stops should be used to minimize travel and reduce damage
due to excessive acceleration. These vertical limit stops
are standard on all Mason precompressed (PC-prefixed) isolation
hangers.
Mason Type SRC Data Sheet
SRC DIMENSIONS
(inches)
Type
& Size |
A |
B |
C |
D
Acceptable Rod Sizes |
SRC-1
SRC-1 1/2
SRC-2 |
1 3/8
1 9/16
1 3/4 |
1/2
5/8
5/8
|
1x1x1/4
1 1/2x1 1/2x1/4
2x2x1/4
|
3/8 through 5/8
3/8 through 1
3/8 through 1 1/4
|
 
TYPE CCB DIMENSIONS
(inches)
Mason Type CCB Data Sheet
| Size |
L |
H |
A |
CCB-1 1/2
CCB-2
CCB-2 1/2
CCB-3
CCB-4
CCB-5
CCB-6
CCB-8
CCB-10
CCB-12
CCB-14
CCB-16
CCB-18
CCB-20
CCB-24
CCB-30 |
1 7/8
2 3/8
2 7/8
3 1/2
4 1/2
5 9/16
6 5/8
8 5/8
10 3/4
12 3/4
14
16
18
20
24
30 |
1
1
1 1/8
1 1/8
1 1/8
1 5/16
1 5/16
1 7/16
1 9/16
1 9/16
1 11/16
1 7/8
2
2 1/2
2 1/2
2 1/2 |
15/16
1 3/16
1 7/16
3/4
1
1
1 1/2
2
2 1/2
3
3 1/2
4
4 1/2
5
6
7 1/2 |
SAB & SAS
Anchorage of equipment in seismic zones
is an important part of system restraint. When anchoring to
concrete there are a variety of methods available. Our in
depth research has revealed the best attachments for seismic zones
are made with the wedge type expansion anchors. They provide
the highest design load for the smallest hole size. Since
they are load assisted, they provide excellent resistance to vibration
and shock loads. Their slip potential is actually a positive
feature in seismic applications giving early warning of potential
failure whereas other anchors just fail catastrophically.
Mason offers two types of wedge anchors.
Our SAB seismic anchor bolt is a female wedge utilizing a cap screw
to fasten to equipment. This design is for use with restrained
mounts where periodic removal and inspection of the mounts may be
required. The benefit is that they do not require lifting
of mounts or equipment over a stud.
Mason's SAS seismic anchor stud is the
same wedge design as the SAB anchor but with a stud instead of bolt,
for attachment. We offer this form for suspension applications
such as with our SCB, seismic cable brace system, for use on piping
and suspended equipment.
Mason Type SAB Data Sheet
SAB ANCHOR BOLTS
(In Stone Aggregate Concrete Fc = 3000 PSI)
Type
&
Size |
Embedment
(in) |
Standard
Tension
(lbs.) |
Tension
with UBC
Inspection*
(lbs.) |
Shear
(lbs.) |
Anchor |
Cap Screw
CS
(in) |
A
(in) |
B
(in) |
SAB-3/8
SAB-1/2
SAB-5/8
SAB-3/4
SAB-1 |
2-5/8
3-1/2
4-3/8
5-1/4
5-3/4
|
720
1010
2220
2330
3660 |
1440
2020
4440
4660
7320
|
1050
1830
2970
3340
6610
|
2-5/16
3-1/16
3-13/16
4-5/8
5 |
1/2
5/8
7/8
1
1-1/4 |
3/8-16UNC x 1-1/4
1/2-13UNC x 1-1/2
5/8-11UNC x 1-3/4
3/4-10UNC x 2-1/4
1 - 8UNC x 2-1/2 |
*These tension values are applicable when
the anchors are installed with special inspection as set forth in
Section 306 of the UBC code.
Shear and Tension values are for anchors
installed in stone aggregate concrete having 3000 PSI minimum compressive
strength at the time of installation.
Values are for anchors installed with a
minimum spacing of 12 diameters on center and with a minimum edge
distance of six diameters. Spacing may be reduced to six diameters
provided the values are reduced 50 percent. Edge distance
may be reduced to three diameters provided the values for shear
are reduced 50% and the values for tension are reduced 30%.
Linear interpolation may be used for intermediate spacings and edge
margins.
Ratings may not be increased to accommodate
periodic loads such as those from wind or seismic forces.
Mason Type SAS Data Sheet
SAS ANCHOR STUDS
(In Stone Aggregate Concrete Fc = 4500 psi)*
Type
&
Size |
Embedment
(in) |
Standard
Tension
(lbs.) |
Tension
with UBC
Inspection**
(lbs.) |
Shear
(lbs.) |
Anchor |
A
(in) |
B
(in) |
C
(in) |
SAS-3/8
SAS-1/2
SAS-5/8
SAS-3/4
SAS-1 |
2 1/8
3 1/4
3 1/2
5 1/2
4 3/4
|
620
1210
1495
2970
4815 |
1245
2425
2990
5945
9635
|
1325
2460
3430
5415
9355
|
3
4 1/4
5
7
9 |
3/8
1/2
5/8
3/4
1 |
1 1/4
1 1/2
1 3/4
2
2 1/4 |
*Testing is being completed for 3000 psi.
*These tension values are applicable when
the anchors are installed with special inspection as set forth in
Section 306 of the UBC code.
Values are for anchors installed with a
minimum spacing of 12 diameters on center and with a minimum edge
distance of six diameters. Spacing may be reduced to six diameters
provided the values are reduced 50 percent. Linear interpolation
may be used for intermediate spacings and edge margins.
Ratings may not be increased to accommodate
periodic loads such as those from wind or seismic forces.
|